Detail Acquisition Measurement Control
Maths Functions
18 Point user linearisation, Max / Min ( Peak/ Valley) memory
Square root, S.G. Correction, Zero, Tare
Alarm Functions
High, Low, Deviation ( band) , on delay time, off delay time, hysterisis, output
selection ( one alarm can switch more than one output)
Outputs energised or de-energised in the alarm state
PID Control ( T331 & 332 Models only)
Type: PID with Auto-tune, PWM Logic or Analogue outputs
Control Action: Reverse, Direct or Heat / Cool
PWM Cycle Times: 0.1Sec to 30mins ( Independent per output)
Auto / Manual switching: Via logic input ( T340) or Communications
Load and Partial Electrical Load Failure Function ( PWM outputs only)
A/ D Converter
Type: Sigma Delta, Resolution: 20 Bit plus Sign
Drift with temperature: 150dB / > 70dB ( 50 & 60Hz)
Thermocouple/ RTD Measurement
Linearised ranges: Types J, K, T, N, B, S, R Thermocouples and
3 wire RTD Pt100 ( alpha = 385) and Pt100 ( alpha = 392)
Typical accuracy: Base Metal ± 0.5° C, Rare Metal ± 1.2 ° C,
RTD 0.3° C. Engineering units: ° C, ° F or Kelvin
RTD Excitation current 0.25mA ( Nom)
Thermocouple ageing feature and open circuit alarms
DC Voltage, Current & Resistance Inputs
Ranges ( Impedance) : ± 100mV( 1000M) ,
± 10VDC( 1M) and ± 20mA(